Please use this identifier to cite or link to this item:
http://dspace2020.uniten.edu.my:8080/handle/123456789/20776
Title: | An experimental work on effect of bending down conductor with reinforced concrete | Authors: | Ariffen A.M. Arshad S.N.M. Ab Kadir M.Z.A. Jasni J. Halim N.H. #PLACEHOLDER_PARENT_METADATA_VALUE# #PLACEHOLDER_PARENT_METADATA_VALUE# #PLACEHOLDER_PARENT_METADATA_VALUE# #PLACEHOLDER_PARENT_METADATA_VALUE# #PLACEHOLDER_PARENT_METADATA_VALUE# |
Issue Date: | 2020 | Abstract: | Down conductor is one of the pivotal parts of the Lightning Protection System (LPS) that diverting the lightning current captured by the air termination system to the earth termination system in each protected structure. A straight down conductor, is ideally suited for the best-case scenario regarding reliability and safety protection. One to aesthetical aspects, down conductor is undesirably bent in most current buildings. However, only the primary bare type of a down conductor is undergone such process, and bent at a certain degree which depending on the structure itself. Hence, this study is to investigate the bending degree effect on down conductors, by looking at breakdown voltage around the bent area with the presence of concrete wall and reinforcement bar. This experimental work conducted on a reduced scale of reinforced concrete which tested with high impulse voltage. It was determined that the bending down conductors has a significant effect on the bent (vertex) area with the interaction of concrete wall and reinforcement bar. © Published under licence by IOP Publishing Ltd. | URI: | http://dspace2020.uniten.edu.my:8080/handle/123456789/20776 |
Appears in Collections: | UNITEN Ebook and Article |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
An experimental work on effect of bending down conductor with reinforced concrete.pdf | 60.24 kB | Adobe PDF | View/Open |
Google ScholarTM
Check
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.